Device Comparisons

Compare devices side by side

Choose 2 to 4 devices, or open an editor-picked comparison.

Free Compare

Build your own comparison

Clear
Selected Devices

Carlo Gavazzi EM540 vs Acrel ADL3000-E

Install fit
Phase support 2-phase 3-wire; 3-phase 3-/4-wire including wild-leg; 120-240 V L-N, 208-415 V L-L, 45-65 Hz. Three-phase four-wire (3P4W); ADL3000-E-A direct-input and ADL3000-E-B CT-input variants.
Installation Indoor 3-DIN DIN-rail direct-connected energy analyzer for low-voltage switchboards. Indoor DIN35 rail three-phase meter; direct-connect ADL3000-E-A and CT-input ADL3000-E-B variants are documented.
Measurement Direct TRMS bidirectional active/reactive/apparent energy and power, demand, PF, frequency, and current/voltage THD to the 15th harmonic; non-MID XS1X. Three-phase electrical parameters, demand, harmonics, and forward/reverse active and reactive energy.
Max current 65 A 80 A
Meter fit
Accuracy class Class 1 active energy; Class 2 reactive energy; XS1X is non-MID. 0.5s kWh accuracy.
Current sensing Direct 5(65) A input; 0.25 A minimum and 20 mA start-up current; no external CT. ADL3000-E-A: direct 3 x 10(80) A. ADL3000-E-B: external-CT input 3 x 1(6) A. The 80 A family maximum applies only to the direct-input A variant.
Monitoring
Protocol RS485 Modbus RTU RS485 Modbus RTU
Local API Yes Yes
Cloud dependency No vendor cloud required for core use; EM540DINAV23XS1X exposes local RS485 Modbus RTU data. No cloud required for core metering. Local data uses RS-485 Modbus RTU; confirm the ordered communication configuration.
Home Assistant Yes Yes
Solar fit
Solar import/export Yes Yes
Buying context
Availability North America, Europe and UK; XS1X carries cULus, CE and UKCA. Local stock varies. Global Acrel product range; ADL3000-E-B/KC is noted by Acrel for North America market certification context, while local distributor availability varies.
Source check
Last verified Oct 3, 2026 Sep 6, 2026
Product page Official page Official page