Eastron SDM54-DM vs Acrel ADL3000-E

Install fit
Phase support 1P2W and 3P4W supplies. Three-phase four-wire (3P4W); ADL3000-E-A direct-input and ADL3000-E-B CT-input variants.
Installation Indoor DIN-rail direct-connected installation by a qualified electrician; IP51 front protection. Indoor DIN35 rail three-phase meter; direct-connect ADL3000-E-A and CT-input ADL3000-E-B variants are documented.
Measurement Direct-connected RMS parameter and bidirectional active/reactive import-export energy measurement for 1P2W and 3P4W AC supplies. Three-phase electrical parameters, demand, harmonics, and forward/reverse active and reactive energy.
Max current 45 A 80 A
Meter fit
Accuracy class Active energy Class 1.0 / Class B (EN 50470-3:2022); reactive energy Class 2. 0.5s kWh accuracy.
Current sensing Direct connection up to 45 A; no external CTs. ADL3000-E-A: direct 3 x 10(80) A. ADL3000-E-B: external-CT input 3 x 1(6) A. The 80 A family maximum applies only to the direct-input A variant.
Monitoring
Protocol RS485 Modbus RTU RS485 Modbus RTU
Local API Yes Yes
Cloud dependency No vendor cloud required; readings are available locally over RS485 Modbus RTU. No cloud required for core metering. Local data uses RS-485 Modbus RTU; confirm the ordered communication configuration.
Home Assistant Yes Yes
Solar fit
Solar import/export Yes Yes
Buying context
Availability Global Eastron product range; regional distributor availability varies. Global Acrel product range; ADL3000-E-B/KC is noted by Acrel for North America market certification context, while local distributor availability varies.
Source check
Last verified Sep 3, 2026 Sep 6, 2026
Product page Official page Official page
Documentation Official docs Official docs